Main Relay Connections
8. Refer to Figure 3 or 4 and 6 when connecting to the main relay.
9. Pull approximately 9" (23 cm) of cable through conduit and strip
10. Attach leads to terminal block as shown in Figure 3 or 4.
11. Check that all wires are held tightly in place by lightly pulling each conductor.
Auxiliary Relay Connections - ADVANCED ONLY
12. Refer to Figure 3 or 4 and 7 when connecting to the auxiliary relay.
13. Pull approximately 2.5" (6 cm) of cable through conduit and strip
14. Attach leads to terminal block as shown in Figure 7.
15. Check that all wires are held tightly in place by lightly pulling each conductor.
Remote Probe Connections
16. Refer to Figure 8 or 9 and 10 when connecting the remote probe.
17. Pull approximately 2.5" (6 cm) of cable through conduit and strip
18. Connect factory supplied cable to terminals block as shown in Figure 10.
19. Check that all wires are held tightly in place by lightly pulling each conductor.
20. Replace cover.
21. Tighten set screw to lock cover in place.
22. Loosen the remote probe housing cover screws and remove cover.
CAUTION: IF THE UNIT WAS SUPPLIED WITH A GASKET AVOID FOLDING, CUTTING, OR TEARING
GASKET. DAMAGING THE GASKET CAN ALLOW MOISTURE TO ENTER THE ENCLOSURE AND
DAMAGE THE UNIT.
23. Pull approximately 4" (10 cm) of cable through conduit and strip
24. Connect factory supplied cable to terminals block as shown in Figure 3 or 4.
25. Check that all wires are held tightly in place by lightly pulling each conductor.
26. Reinstall the gasket, if necessary.
27. Replace cover and tighten screws to 60 in-lb (6.8 n-m) of torque.
VRF180913 Rev. A
/
" (6 to 7 mm).
1
4
/
" (6 to 7 mm).
1
4
/
" (4 to 5 mm).
3
16
/
" (4 to 5 mm).
3
16
9
9