Disconnects must meet the following requirements:
• Located in close proximity to the device
• Easily accessible to the operator
• Appropriately marked as the disconnect for the device and associated circuit
• Sized appropriately to the requirements of the protected circuit (See Specifications)

PROTECTIVE EARTH GROUND

To eliminate shock hazards in the unlikely event of an internal insulation breakdown, the unit is provided with
an "earth" lead which must be connected to earth ground. In addition, the input power ground lead must be
connected to the "protective earth" (
carry the sum total of all circuits' maximum amperage.
CONDUIT-CABLE CONNECTION
Two threaded female conduit openings are provided in the housing for input and output wiring. When only one
conduit opening is used for installation, the unused opening must be sealed with a suitable type 4X/IP66 plug
with pipe sealant in order to maintain approval requirements.

ELECTRICAL CONNECTIONS

Note: The VRF II Series can be operated from 120-240 VAC 50/60 Hz or 24-48 VDC and provides reverse polarity
protection in the event of a wiring error.

VRF II SERIES INTEGRAL MODEL ONLY

Input Power Connections
1. Refer to Figures 3 or 4 and 5 when connecting input power to the unit.
2. Loosen the housing cover screws and remove cover.
CAUTION: IF THE UNIT WAS SUPPLIED WITH A GASKET AVOID FOLDING, CUTTING OR TEARING
GASKET. DAMAGING THE GASKET CAN ALLOW MOISTURE TO ENTER THE ENCLOSURE AND
DAMAGE THE UNIT.
Note: Two threaded female conduit openings are provided in the housing to separate input and output wiring.
3. Pull approximately 4" of cable through conduit closest to the grounding bracket and strip as follows:
a.
Ground –
/
3
8
b. Power Leads –
4. Attach incoming ground lead to grounding bracket as shown in Figure 3 or 4.
VRF180913 Rev. A
) terminal provided. Wire sizes must be selected such that it can safely
" (9 to 10 mm)
/
" (6 to 7 mm)
1
4
7
7
www.bindicator.com