Regulatory Compliance - Honeywell Novar ES3.S Mounting And Wiring Instructions

Executive controller

Advertisement

NOVAR ES3.S EXECUTIVE CONTROLLER
Universal Input Configuration Switches:
Two switches are provided to select either universal input mode or current mode for the Outdoor Temperature Sensor
(OTS) and Outdoor Light Sensor (OLS) inputs. Refer to Table 5 for input configuration settings.
Switch Position
OTS
1
4-20mA current loop type input enabled
ON
OTS
2
Universal input type selected: 0-10V, Type 3 10K thermistor, 0-100K ohm resistive, digital.
OFF
OLS
1
4-20mA current loop type input enabled
ON
OLS
2
Universal input type selected: 0-10V, Type 3 10K thermistor, 0-100K ohm resistive, digital.
OFF
1
Factory default position
2
See section 'Wiring' for proper wiring when using this mode.
MODEL AND PART NUMBERS
The part numbers provided in Table 6 should be used to order the appropriate Novar parts.
Novar ES3.S Executive Controller - Incl. plan controller, electronics and bottom metal
cover, drop in design compatible with the original XCM.10S and Savvy base-plate
Outdoor Temperature Sensor (4- 20mA)
Outdoor Light Sensor, Analog (4- 20mA; 300-0 Foot-candles)
Outdoor Light Sensor, Analog (4- 20mA; 1500-0 Foot-candles)
ALS 5K
40VA Transformer
22 AWG Shielded Low CAP CMP- CL3P Communications Color: White Wire Spec:
EIA/TIA 485

REGULATORY COMPLIANCE

This device has been tested and found to be in compliance with the requirements set forth in UL 916 5th Edition, Energy
Management Equipment, and is listed by Underwriters Laboratories, Inc., for installations in the United States.
This device has been tested and found to be in compliance with the requirements set forth in C22.2, No. 205-17 3rd
Edition, and is Certified by Underwriters Laboratories, Inc., for installations in Canada.
Federal Comms. Commission (FCC)
This equipment has been tested and found to comply with the Federal Communications Commission (FCC) CFR 47 Part
15 Subpart B for the United States.
These limits are designed to provide reasonable protection against such interference when operated in a commercial
environment Operation of this equipment in a residential area may cause interference, in which case, users at their own
expense will be required to take whatever measures may be required to correct the interference. Any unauthorized
modification of this equipment may result in the revocation of the owner's authority to continue its operation.
Innovation, Science and Economic Development Canada (ISED)
ISED Standard: ICES-003 Issue 7
Operation is subject to the following two conditions.
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
31-00366—01
Table 5. Configuration Switch Table
Table 6. Novar Part Numbers.
Product Name
12
Selected Mode
Part No.
ES3.S
ES3.S
Executive
Controller
OTS-2
735070000
ALS-300
708100000
ALS-1.5K
708101000
ALS 5K
813000101
-
730090000
-
33201001