Components List; Provided Components; Frame Installation - Daintree GE current Lumination LRX Series Installation Manual

Led luminaire

Advertisement

Lumination
(LRX - Series)
®
Prepare Electrical Wiring
Electrical Requirements
• The luminaire must be supplied with 120-277 VAC,
50/60 Hz (In 120-277V application).
• Connected to an individual properly grounded branch
circuit, protected by a 15 or 20 ampere circuit breaker. Use
min. 75°C supply conductor.
Grounding Instructions
• The grounding and bonding of the overall system
shall be done in accordance with National Electric
Code (NEC) Article 600 and local codes.

Provided Components

The components have been properly packed to avoid damage during transit. Inspect the components to confirm there is no physical damage.
Do not install damaged components.
LRXEMBBKIT07HE/LRXEMBBKIT07/LRXEMBBKIT10 Installation

Frame Installation

1
Before retrofit, verify that the junction box and bracket in the
existing installation are metal and are constructed similarly to
the illustration above.
Fixture Requirements
The units covered by this install instruction are intended to retrofit
listed surface mounted luminaires, as well as type Non-IC recessed
mounted fluorescent type luminaires. Please review Step 1 for an
example existing fixture depiction.

Components List

Provided Item
1 LRX EMBB Frame Kit
2 LRX EMBB Fixture
Suitable Frame
Size (in.)
Shape
Dimensions (in.)
4
Round
12.60 x 7.64 x 3.54
6
Round
12.60 x 7.64 x 3.54
8
Round
15.55 x 11.34 x 3.54
4
Square
12.60 x 7.64 x 3.54
6
Square
13.35 x 11.34 x 3.54
8
Square
13.35 x 11.34 x 3.54
3
Installation Guide
Bracket
Hole
Suitable
Fixture
Size (in.)
4.20-5.50
LRXR4xxxxxxx
5.91-6.50
LRXR6xxxxxxx
7.68–8.27
LRXR8xxxxxxx
4.20-5.50
LRXS4xxxxxxx
5.95-7.50
LRXS6xxxxxxx
7.95-9.50
LRXS8xxxxxxx