FACTORY SETTINGS (DEFAULT)

Language
Country
Date
Time
Operation mode
Heating cable type
Pipe diameter
Insulation thickness
SET temperature
Minimum ambient temperature
Heating in sensor failure mode
Low temperature limit
High temperature limit
Low temperature alarm
High temperature alarm
Alarm sound
Key lock

ERROR / ALARMS AND TROUBLESHOOTING

Error Code
E:2.1
E:2.2
E:2.3
E:2.4
E:3.1
E:3.2
E:4.1
E:4.2
E:5
E:6.0
E:6.1
E:6.2
E:6.3
E:6.4
E:6.5
E:6.6
RAYCHEM-OM-EU1838-ELEXANT450c-ML-2103
English
None; To be selected
01/01/2018 or last saved date
00:00 or last saved time
To be selected
To be selected
DN 25
30 mm
+3°C
–15°C
ON
–40°C
+85°C
0°C
+65°C
OFF
ON
Elexant 450C
SENSOR_1_OPEN
SENSOR_1_SHORT
SENSOR_2_OPEN
SENSOR_2_SHORT
SENSOR_1_TEMP_HIGH
SENSOR_2_TEMP_HIGH
SENSOR_1_TEMP_LOW
SENSOR_2_TEMP_LOW
n/a
n/a
INTERNAL_ERROR
INTERNAL_ERROR_RTC
INTERNAL_ERROR_PM
INTERNAL_ERROR_ADC
INTERNAL_ERROR_IP
n/a
Remedy
Check sensor connection
Check sensor and replace it
Check sensor connection
Check sensor and replace it
Sensor 1 High temperature alarm
Sensor 2 High temperature alarm
Sensor 1 Low temperature alarm
Sensor 2 Low temperature alarm
Replace unit
Replace unit
Replace unit
Replace unit
Replace unit