nVent RAYCHEM Elexant 450c Operation Manual page 6

Hide thumbs Also See for Elexant 450c:

Advertisement

Available languages

Available languages

Heating Cable & Pipe
Min. expected ambient
temperature
Cable type
XL-TRACE -1
Cable type
XL-TRACE -2
Pipe diameter
Low temperature alarm
High temperature alarm
RAYCHEM-OM-EU1838-ELEXANT450c-ML-2103
Heating
Heating
zone 1
zone 2
Example
Example
–15°C
/ –15°C
15XL2-ZH
15XL2-ZH
DN 25
/ DN 25
0°C
/ 0°C
+65°C
+65°C
Parameters
Range: –40°C to 0°C
Default: –15°C
Heating cable range:
10XL2-ZH
15XL2-ZH
26XL2-ZH
31XL2-ZH
FS-C10-2X
Other systems
Default: ---
Heating cable range:
10XL2-ZH
15XL2-ZH
26XL2-ZH
31XL2-ZH
FS-C10-2X
Other systems
Default: ---
Range: DN 10 - DN 125
Default: DN 25
Standard NTC Sensor:
Range : –40°C to +78°C
Default: 0°C
PT-100 Sensor with
SM-PT-100-2:
Range: –40°C to +245°C
Default: 0°C
Standard NTC Sensor:
Range : +2°C to +90°C
Default: +65°C
PT-100 Sensor with
SM-PT-100-2:
Range: +2°C to +250°C
Default: +65°C
Note
Sensor PASC (AMBIENT)
The temperature is the minimal outdoor
temperature to be expected and will be
used for the ambient temperature (PASC)
algorithm only. It will set the correct duty
cycle for an optimized and energy saving
operation. If the ambient temperature is
below this set point, the relay is 100% ON.
Select the temperature by using
the + / – keys.
Select the type of nVent RAYCHEM heating
cable used in your installation, connected to
heating zone 1.
Other system can be used if the heating
cable type is not known or listed.
Select the type of nVent RAYCHEM heating
cable used in your installation, connected to
heating zone 2.
Other system can be used if heating cable
type is not known or listed.
Assign the correct pipe diameter per
heating zone 1 and/or 2.
You can change the value from DN 10 up
to DN 125.This has impact in the ambient
temperature sensing mode to define the
correct duty cycle.
Note: In case of multiple pipe sizes per
heating zone, select the bigger size of the
pipe network.
To determine the low temperature limit.
When the value is reached, a warning will
appear on the screen. The buzzer tone will
be active.
The relay will be continuously ON and will
not interrupt the unit's functioning. The info
status main screen will show the actual
pipe temperature.
To determine the high temperature limit; A
warning will appear on the screen when the
value is reached.
The relay will be continuously OFF and will
not interrupt the unit's functioning.
Value range:
+2°C to +90°C /Standard NTC sensor
+2°C to +250°C /Sensor module
SM-PT-100-2 for PT-100
nVent.com/RAYCHEM
|
6