Boiler Dimensions & Ratings - PeerlessBoilers WV-DV Series Installation, Operation & Maintenance Manual

Oil boilers
Table of Contents

Advertisement

8. BOILER DIMENSIONS & RATINGS
Figure 8.1: Boiler Views
Boiler
Jacket
Model
Depth
Number
"A"
WVDV-03
14-1/8"
WVDV-04
18-1/8"
Table 7.1: Boiler Ratings
Model
Number¹
GPH
WV-DV-03
0.75
WV-DV-04
1.15
WV-DV-04
1.30
1 Boiler Model No. may have the following suffix letters: WPC = Water Package w/Burner & Circulator; WPCT = Water Package w/Burner,
Circulator & Tankless Coil.
2 Firing rate is based on a fuel oil with a heating value of 140,000 BTU per gallon. Burner input based on maximum altitude of 2,000 ft. – for other
altitudes consult factory.
3 Net water ratings based on an allowance of 1.15. Consult Factory before selecting a boiler for installations having unusual piping and pickup
requirements, such as intermittent system operation, extensive piping systems, etc.
4 Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S. Government test.
5 Must be used with factory supplied 4" flexible insulated venting system.
Jacket
Jacket
Width
Height
"B"
"C"
22-1/8"
35"
22-1/8"
35"
Series WV-DV™
Input²
Heating
Capacity
MBH
MBH
105
92
161
141
182
158
BOILER DIMENSIONS & RATINGS
Rear of Jacket
to c/l of Vent
"D"
7-1/16"
9-1/16"
Net Ratings
,
Water
,
4
3
MBH
80
122
137
Right Side of
Vent Size
Jacket to
Diameter
c/l of Vent
"F"
"E"
8-5/16"
4"
8-5/16"
4"
Content,
AFUE
,
4
%
86.7
86.7
86.0
Water
gal
11.75
14.75
14.75
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wv-dv-03-075Wv-dv-04-115Wv-dv-04-130Wv-dv-03Wv-dv-04

Table of Contents