Start-up and adjustment recommendations: Above Turbulator, Pin, Air Damper, and Air Dial settings are start-up settings only. Adjust burner for highest
CO ² (no more than 13.1%) while maintaining a 0 smoke spot. Pressure or draft over fire and in flue cannot be adjusted. However, draft and/or pressure
measurements must be taken in these two locations and recorded for reference. All adjustments and measurements must be made using suitable
instruments such as those found in a Bacharach Combustion Test Kit.
Factory Installed Nozzles are indicated in Boldface.