Gavita Pro SL2 Series Manual page 6

Table of Contents

Advertisement

7.5
Connecting up to 500 or 1000 fixtures
Using a setup with daisy chained splitters, up to 500 fixtures on EL1 and 1000 fixtures on EL2 (over two channels) can be
connected as shown in fig. 10.
Use the black controller cable (item comes with the controller) to connect the primary channel of the controller to the input
port of the first splitter (10A).
Remove the dummy from the input port of the fixtures (8).
Note: Keep the dummy in a safe place! The dummy is necessary to operate the fixture in standalone mode.
Use a grey 6PC6 modular jack interconnect cable (item 3.) to connect the output port of the splitter to the input port of the
first fixture (10C).
Use a grey 6PC6 modular jack interconnect cable (item 3.) to connect the output port of the first fixture to the input port of
the second (10D).
Repeat these steps to connect up to 100 fixtures per splitter output port (10E). Up to 500 fixtures can be connected to the
primary channel.
Snap-on two grey ferrite cores (item 4.) on the grey interconnect cable (item 3.) close to the 6P6C plugs.
Use the grey 6PC6 modular jack interconnect cables (item 3.) to connect the outport of a splitter to the inport of the next
(10B).
Use the black secondary channel (item comes with controller) (10G) to connect another 500 fixtures, in the same way the
fixtures are connected to the primary channel.
Warning! Ensure the power cord and the controller cables do not touch any of the reflectors.
Avertissement! Assurez-vous que le cordon d'alimentation et que les câbles de contrôle ne touchent aucun des réflecteurs.
Warning! Distribute number of fixtures evenly over daisy chains.
Avertissement! Distribuez uniformément le nombre de dispositifs sur les chaînettes en sangle.
Warning! Ensure the repeater bus connections are integrated in a correctly set up installation for best results.
Avertissement! Assurez-vous que les raccordements de barres omnibus répéteurs sont adéquatement intégrés dans les
limites d'une bonne installation pour obtenir les meilleurs résultats.
Warning! Boosters should never be used to expand.
Avertissements! Ne jamais utiliser survolteurs pour étendre.
Warning! The maximum cable length per splitter is 250m (100 interconnect cables).
Avertissement! La longueur maximale de câblage par séparateur est de 250 m (100 câbles de liaison).
G
A
10.
B
401
402
301
302
201
202
101
102
C
D
1
2
501 - 1000
F
500
400
300
200
E
100