Mitsubishi Electric EHSD-MED Service Manual page 58

Hydrobox
Table of Contents

Advertisement

<Thermistors Characteristics Charts>
• Room temperature thermistor (TH1)
• Refrigerant liquid temperature thermistor (TH2)
• Flow water temperature thermistor (THW1)
• Return water temperature thermistor (THW2)
• DHW tank water temperature thermistor (THW5A/5B)
• Zone1 flow temperature thermistor (THW6)
• Zone1 return temperature thermistor (THW7)
• Zone2 flow temperature thermistor (THW8)
• Zone2 return temperature thermistor (THW9)
Thermistor R0 = 15 kΩ ± 3%
B constant = 3480 ± 2%
1
1
Rt = 15exp {3480 ( 273+t – 273 )}
0°C
15 kΩ
10°C
9.6 kΩ
20°C
6.3 kΩ
25°C
5.2 kΩ
30°C
4.3 kΩ
40°C
3.0 kΩ
• Boiler flow temperature thermistor (THWB1)
• Mixing tank temperature thermistor (THW10)
Thermistor R100 = 3.3 kΩ ± 2%
B constant = 3970 ± 1%
1
1
Rt = 3.3 exp {3970 ( 273+t – 273 )}
0°C
162.8 kΩ
10°C
97.4 kΩ
20°C
60.3 kΩ
25°C
48.1 kΩ
30°C
38.6 kΩ
40°C
25.4 kΩ
50°C
17.1 kΩ
60°C
11.9 kΩ
70°C
8.4 kΩ
80°C
6.0 kΩ
OCH712C
50
40
30
20
10
0
-20 -10 0 10 20 30 40 50
Temperature (°C)
1000
900
800
700
600
500
400
300
200
100
0
-30 -20 -10 0 10 20 30 40 50 60 70 80
Temperature (°C)