Mitsubishi Electric EHSD-MED Service Manual page 29

Hydrobox
Table of Contents

Advertisement

Mixing valve control
1. From the Auxiliary settings menu, highlight Mixing valve control.
2. Press CONFIRM.
3. The Mixing valve control screen is displayed.
4. Use F1 and F2 buttons to set Running time between 10 to 240 seconds. The Running time equals to
a period from full open of the valve (at a hot water mixing ratio of 100%) to full close (at a cold water
mixing ratio of 100%).
Note: Set the Running time according to the specifications of the actuator of each mixing valve.
1. From the Auxiliary settings menu, highlight Mixing valve control.
2. Press CONFIRM.
3. The Mixing valve control screen is displayed.
4. Press F3 and F4 buttons to set the interval between 2-zone temperature controls of the mixing valve
between 1 to 30 minutes.
Note: It is recommended to set the interval to 2 minutes that is a default value. With the interval
set longer, it could take longer to warm up a room.
Flow sensor
1. From the Auxiliary settings menu, highlight Flow sensor.
2. Press CONFIRM.
3. Press F3 or F4 buttons to select a refrigerant address of which you wish to configure or check the
settings, and press CONFIRM. *1
4. The Flow sensor screen is displayed.
5. Use F1 and F2 buttons to set the minimum flow rate of flow sensor between 0 to maximum L/min.
6. Use F3 and F4 buttons to set the maximum flow rate of flow sensor between minimum to 100L/min.
*1 For multiple outdoor units control system only.
Note: Do not change the setting since it is set according to the specification of Flow sensor
attached to the hydrobox.
<Heat source setting>
The default heat source setting is heat pump and all electric heaters present in the system to be
operational. This is referred to as Standard operation on the menu.
<Pump speed>
1. From the Service menu, highlight Pump speed.
2. Press CONFIRM.
3. Press F3 and F4 buttons to select a refrigerant address of which you wish to configure or check the
settings, and press CONFIRM. *1
4. The Pump speed screen is displayed.
5. Use F1 and F2 buttons to set the pump speed (1 to 5) of DHW operation.
6. Use F3 and F4 buttons to set the pump speed (1 to 5) of space heating(cooling) operation.
*1 For multiple outdoor units control system only.
OCH712C
Mixing valve control setting screen
29
Flow sensor setting screen
Heat source setting screen
PUMP SPEED
Pump speed setting screen