Mitsubishi Electric EHSD-MED Service Manual page 31

Hydrobox
Table of Contents

Advertisement

<Energy monitor settings>
1. General description
End user can monitor accumulated (*
*
Monthly and Year to date
1
*
- DHW operation
2
- Space heating
- Space cooling
Refer to the menu tree in "9-3. Main Settings Menu" for how to check the energy, and "6-6. DIP switch functions" for the details on DIP-SW setting.
Either one of the following 2 methods is used for monitoring.
Note: Method 1 should be used as a guide. If a certain accuracy is required, method 2 should be used.
(1) Calculation internally 【Method 1】
Electricity consumption is calculated internally based on the energy consumption of outdoor unit, electric heater, water pump(s) and other auxiliaries.*
Delivered heat is calculated internally by multiplying delta T (Flow and Return temp.) and flow rate measured by the factory fitted sensors.
Set the electric heater capacity and water pump(s) input according to indoor model name and specs of additional pump(s) supplied locally. (Refer to the menu
tree in "9-3. Main Settings Menu")
Booster heater1
Default
EHSD-MED
EHSD-VM2D
EHSD-VM6D
EHSD-YM9D
EHSD-YM9ED
EHSD-TM9D
EHSC-MED
EHSC-VM2D
EHSC-VM6D
EHSC-YM9D
EHSC-YM9ED
EHSC-TM9D
ERSD-VM2D
ERSD-VM6D
ERSD-YM9D
ERSC-MED
ERSD-MED
ERSC-VM2D
ERSC-VM6D
ERSC-YM9D
EHSE-MED
EHSE-YM9ED
ERSE-MED
ERSE-YM9ED
EHPX-MED
EHPX-VM2D
EHPX-VM6D
EHPX-YM9D
EHPX-YM9ED
ERPX-MD
ERPX-VM2D
ERPX-VM6D
ERPX-YM9D
*1 When the hydrobox is connected with a PUHZ-FRP or PUMY models, electricity consumption is not calculated internally. To display the electricity consumption,
conduct the method 2.
*2 "***" displayed in the energy monitor setting mode means the factory fitted pump is connected as Pump 1 so that the input is automatically calculated.
When anti-freeze solution (propylene glycol) is used for primary water circuit, set the delivered energy adjustment if necessary.
For further detail of above, refer to the menu tree in "9-3. Main Settings Menu".
(2) Actual measurement by external meter【Method 2】 (locally supplied)
FTC has external input terminals for 2 'Electric energy meters' and a 'Heat meter'.
If two 'Electric energy meters' are connected, the 2 recorded values will be combined at the FTC and shown on the main remote controller.
(e.g. Meter 1 for H/P power line, Meter 2 for heater power line)
Refer to the [Signal inputs] in "6. WIRING DIAGRAM" for more information on connectable electric energy meter and heat meter.
● Connectable electric energy meter and heat meter
Voltage free contact for 12 VDC detection by FTC (TBI.3 1, 3 and 5 pin have a positive voltage.)
Pulse meter type
Minimum ON time: 40 ms
Pulse duration
Minimum OFF time: 100 ms
0.1 pulse/kWh
Possible unit of pulse
100 pulse/kWh
Those values can be set by the main remote controller. (Refer to the menu tree in "9-3. Main Settings Menu".)
OCH712C
1
) 'Consumed electrical energy' and 'Delivered heat energy' in each operation mode (*
Booster heater2
2 kW
4 kW
0 kW
0 kW
2 kW
0 kW
2 kW
4 kW
3 kW
6 kW
3 kW
6 kW
3 kW
6 kW
0 kW
0 kW
2 kW
0 kW
2 kW
4 kW
3 kW
6 kW
3 kW
6 kW
3 kW
6 kW
2 kW
0 kW
2 kW
4 kW
3 kW
6 kW
0 kW
0 kW
0 kW
0 kW
2 kW
0 kW
2 kW
4 kW
3 kW
6 kW
0 kW
0 kW
3 kW
6 kW
0 kW
0 kW
3 kW
6 kW
0 kW
0 kW
2 kW
0 kW
2 kW
4 kW
3 kW
6 kW
3 kW
6 kW
0 kW
0 kW
2 kW
0 kW
2 kW
4 kW
3 kW
6 kW
1 pulse/kWh
1000 pulse/kWh
Pump1 * 2
Pump2
***(factory fitted pump)
0 kW
***
***
***
***
***
***
***
***
***
***
***
***
***
***
***
***
When additional pumps supplied locally are
***
connected as Pump2/3, change setting ac-
cording to specs of the pumps.
***
***
***
***
***
***
***
***
***
***
***
***
***
***
***
***
10 pulse/kWh
31
2
) on the main remote controller.
1
Pump3
0 kW