Balancing The Unit - Broan ERV90HCS Installation Instructions Manual

Fresh air systems
Hide thumbs Also See for ERV90HCS:
Table of Contents

Advertisement

Available languages

Available languages

7. BALANCING THE UNIT

To avoid balancing, the difference between stale air ducts total length and fresh air ducts total length must not exceed 50 ft. However,
even if the stale air ducts and fresh air ducts lengths are almost equal, your local building codes may require balancing the unit.
If the unit does not need to be balanced, shut all the pressure taps (located on the unit door) with the small plastic plugs included in the
hardware kit.
7.1 W
N
HAT YOU
EED TO
A magnehelic gauge capable of measuring 0 inch to 0.5 inch of water (0 Pa to 125 Pa) and
2 plastic tubes.
The balancing chart located on the unit door.
7.2 P
S
RELIMINARY
TAGES TO
Seal all the unit ductwork with tape. Close all windows and doors.
Turn off all exhaust devices such as range hood, dryer and bathroom fans.
Make sure the integrated balancing dampers are fully open. Turn the thumb screw (A) clockwise
to manually open the dampers. Both are located on the Exhaust air to outside port and on
Fresh air to building port.
Make sure all filters are clean (if it is not the first time you balance the unit).
7.3 B
P
ALANCING
ROCEDURE
1. Set the unit to high speed.
Make sure that the furnace/air handler blower is ON if the installation is in any way
connected to the ductwork of the cold air return. If not, leave furnace/air handler blower
OFF. If the outside temperature is below 0°C / 32°F, make sure the unit is not running in
defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured
that the unit is not in a defrost cycle.).
2. Place the magnehelic gauge on a level surface and adjust it to zero.
3. Connect tubing from gauge to EXHAUST air flow pressure taps (see diagram beside).
Be sure to connect the tubes to their appropriate high/low fittings. If the gauge drops
below zero, reverse the tubing connections.
NOTE: It is suggested to start with the exhaust air flow reading because the exhaust
has typically more restriction than the fresh air, especially in cases of fully ducted
installations or source point ventilation.
Place the magnehelic gauge upright and level. Record equivalent AIR FLOW of the reading according to the balancing chart.
4. Move tubing to FRESH air flow pressure taps (see diagram). Adjust the fresh air balancing damper until the fresh air flow is
approximately the same as the EXHAUST air flow. If fresh air flow is less than exhaust air flow, then go back and adjust the
exhaust balancing damper to equal the fresh air flow.
5. Secure both dampers thumb screw in place with tape.
6. Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows,
your name, phone number and business address).
NOTE: The unit is considered balanced even if there is a difference of ±10 cfm (or ± 5 l/s or 17 m³/h) between the two air
flows.
B
U
ALANCE THE
NIT
B
U
ALANCE THE
NIT
- 21 -
VP0009
A
VJ0032
P
ORT WITH INTEGRATED BALANCING
- T
DAMPER
OP VIEW
B
ALANCING
C
HART
F
RESH AIR FLOW
1 12 12 11
1 12 12 11
3 13 33 23
1 12 12 11
E
XHAUST AIR FLOW
1 12 12 11
3 13 33 23
VP0015

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Erv90hctHrv90hsHrv90htHrv90hErv90hc

Table of Contents