Choose an appropriate location to install the exterior hoods:
There must be a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination
There must be a minimum distance of 18 inches (457 mm) from the ground
Make sure the intake hood is at least 6 feet (1.8 m) away (or more, as per applicable building codes or standards)
from sources of contamination such as:
• High efficiency furnace vent
• Any exhaust from a combustion source
• Gas meter exhaust, gas barbecue-grill
• Garbage bin
Refer to figure below for connecting insulated ducts to the exterior hoods. An "Anti-gust intake hood" should be installed in regions where
a lot of snow is expected to fall.
E
XHAUST HOOD
VD0028
H
OODS
I
NTAKE HOOD
18"
(457
)
MM
6'
(1.8
)
M
!
WARNING
6" Ø
(152
)
MM
18"
(457
)
MM
O
PTIONAL
DUCT LOCATION
T
APE AND DUCT TIE
- 16 -
6'
(1.8
)
M
18" (457
)
MM