NuTone VX1000C Installation Instructions Manual

NuTone VX1000C Installation Instructions Manual

Built-in central cleaning system
Hide thumbs Also See for VX1000C:

Advertisement

BUILT-IN
CENTRAL CLEANING SYSTEM

INSTALLATION INSTRUCTIONS

For Power Unit Models
VX475, VX550, VX1000,
VX475C, VX550C, VX1000C
To register this product, visit www.nutone.com
Part No. 30042322 rev. D

Advertisement

Table of Contents
loading

Summary of Contents for NuTone VX1000C

  • Page 1: Installation Instructions

    BUILT-IN CENTRAL CLEANING SYSTEM INSTALLATION INSTRUCTIONS For Power Unit Models VX475, VX550, VX1000, VX475C, VX550C, VX1000C To register this product, visit www.nutone.com Part No. 30042322 rev. D...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS SYSTEM PLANNING AND LAYOUT Examples ................. .3 Locating the Power Unit .
  • Page 3: System Planning And Layout

    SYSTEM PLANNING AND LAYOUT The NuTone central cleaning system consists of a power unit, PVC tubing and fittings, wall inlets, a flexible hose and various cleaning attachments. The power unit is designed to be wall-mounted away from the living area of the home and connected to the living area by means of permanently installed in-wall tubing, fittings and inlets.
  • Page 4: Locating The Power Unit

    THE SPLIT-LEVEL HOUSE Like the two-story house, the split level installation commonly calls for a two-level trunk line. Here, the power unit is located in the garage. The intake tubing runs exposed up the garage wall and into the ground level section's attic.
  • Page 5: General Installation Guide

    GENERAL INSTALLATION GUIDE When the federal, provincial or state legislation comprises more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses. TOOL LISTING Depending on your installation, you may require the use of these tools.
  • Page 6 Making a Joint Insert the tube into the fitting, aligning the two parts as they will be installed. Mark the tube and the fitting so that you can quickly realign the joint. See Figure 7. FIGURE 7 Apply cement only to the outside of the tube. Dab the cement generously in an inch-wide band.
  • Page 7: Installation In New Construction

    INSTALLATION IN NEW CONSTRUCTION WALL INLET ROUGH-IN Once the locations for the wall inlets have been determined, mount all inlet brackets. 1. Choose the appropriate mounting bracket for the inlet being installed. (See chart) 396-1 CI335 CI358 CI370 CI390 CI395 CI398 2.
  • Page 8: Installing The Tubing

    INSTALLING THE TUBING Use the following installation guidelines when installing tubing. 1. Start tubing installation at farthest inlet and work toward the power unit. 2. Tubing run to the power unit should be as straight as possible. 3. When assembling sections with elbows and tees, make sure the curve in the fitting is aligned so that the air flows toward the power unit.
  • Page 9: Wall Inlet Installation

    WALL INLET INSTALLATION Model CI370 Wall Inlet (CF361 and CF361F Rough-In) 1. Remove the cardboard plaster guard. 2. Refer to Figure 20. For some drywall or panel construction, the plaster frame will extend beyond the finished wall. In this case, remove plaster frame from mounting bracket by removing mounting screws.
  • Page 10: Model Ci395Rk Electravalve Electrified Inlet Installation

    CI390 & CI395 ELECTRAVALVE ELECTRIFIED INLET INSTALLATION (CI395RK ROUGH-IN) 1. See Figure 27. Fasten the mounting plate to a stud within three studs (48") of an electrical outlet box. Measure and mark the wire 10" from the plug (A). Feed the wire through the top hole in the mounting plate (just above the circular opening).
  • Page 11: Model Ci358 Supervalve Wall Inlet & Rough-In

    C1358 SUPERVALVE™ WALL INLET & ROUGH-IN KIT FIGURE 29 FOR HOUSEHOLD USE ONLY. INSTALL ONLY ON A NOMINAL 120 V, 60 Hz, 7 A SUPPLY PROTECTED BY A MAXIMUM 15 A OVERCURRENT PROTECTIVE DEVICE. THE PIN CONNECTOR ON THIS TYPE A WALL VALVE IS INTENDED FOR USE ON A NOMINAL 120 V, 60 Hz, 7 A SUPPLY ONLY.
  • Page 12: Installation In Existing Construction

    INSTALLATION IN EXISTING CONSTRUCTION LOCATING ACCESS KEYS IN EXISTING CONSTRUCTION Unless your home is a ranch-style house where a single trunk line can run directly through the attic or basement, you should first investigate your house to find the key to running your tubing from level to level.
  • Page 13: Installing Inlet Tubing

    INSTALLING THE INLET TUBING When your planning is complete, you will have to determine where all the inlets and the power unit will be located. You have also mapped out the location of your trunk line and found the access you need to run vertical tubing from one level of your house to another level.
  • Page 14 Drilling the Access Holes Once you are certain that you’ve located the center of the wall directly above the inlet location, use a 2½” hole saw to cut the access hole through the wall plate or header and into the wall cavity. (A 1/2” drill is recommended.) Carefully remove the drill from the hole.
  • Page 15: Wall Inlet Installation

    Whatever the case, insert the completed inlet line into the access hole and thread it down inside the wall. The inlet line should be long enough so that it extends above the joists in the attic; at this height, it can be easily connected to the branch and truck lines.
  • Page 16 Use an awl or icepick to punch pilot holes where you marked the two hole locations. Now, drill two 3⁄8” diameter holes, using the pilot holes as the centers. Locate and drill these holes exactly as marked with the template. Also drill four pilot holes in the four corners of the marked area.
  • Page 17 Hold the assembly in place for a few minutes as the cement sets; allow 5 minutes for the cement to completely dry. Now, strip the ends of the two low voltage wires, and then connect the wires to the screw terminals on the back of the inlet cover.
  • Page 18: Models Ci370 & 360 Wall Inlets

    Insert the bottom screw into the inlet cover and through the other parts. Give the screw a few turns until it firmly engages in the mounting plate. Now, level and slightly lower the assembly. Make sure the wall is sandwiched between the inner and outer parts—you’ll be able to feel if mounting plate is firmly centered on the...
  • Page 19: Model 330 & Ci335 Wall Inlets

    5. Attach the low voltage wires to terminal screws on back of wall inlet (Figure 35). If using 361 Rough-in with CI370 Series Inlets, refer to instructions on page 7, step 3, shown in Figure 10. FIGURE 35 6. Insert wall inlet into bracket and secure with the two screws provided (Figure 36).
  • Page 20: Floor Inlet Installation In New And Existing Construction

    FLOOR INLET INSTALLATION IN NEW & EXISTING CONSTRUCTION Model CI370 or 360 Series Inlets (361 Rough-In) 1. Refer to Figures 41 and 42. After floor inlet location has been selected, cut a 3 ⁄ " x 2 ⁄ " square hole in floor. Center line of inlet must be located at least 2½"...
  • Page 21: Original Vacpan Installation Instructions

    ORIGINAL VACPAN INSTALLATION INSTRUCTIONS NOTE: Please read instructions prior to installation. INSTALLATION TIPS • Plan the location of your ORIGINAL VACPAN to be conveniently located for sweeping clean-ups. • Also consider ease of access of vacuum tube piping connections during installation. •...
  • Page 22 IN WALL INSTALLATIONS Refer to Figure 47. • ORIGINAL VACPAN can be installed between wall studs in side walls. • ORIGINAL VACPAN should be located tight to one side in stud space. • Once the ORIGINAL VACPAN location is determined, cut a 6¾”...
  • Page 23: Original Vacusweep Inlet Valve Installation Instructions

    ORIGINAL VACUSWEEP INSTALLATION INSTRUCTIONS CONNECTION FROM BELOW Refer to Figure 48. 1. Turn the power to the vacuum unit OFF. Measure distance (X) between the kickplate face and the inside edge of the cabinet. Then, add 2 ¾” to the measured distance. See Figure 48-1.
  • Page 24 CONNECTION FROM BEHIND Refer to Figure 49. 1. Turn the power to the vacuum unit OFF. Choose a location under the cabinet for the VacuSweep Valve so that it can be connected to the central vacuum pipe. Measure distance (X) between the kickplate face and the inside edge of the cabinet.
  • Page 25 wire/string to temporarily hold the pipe and elbow in place, insert the VacuSweep ® Inlet Valve into the opening at the base of the wall and elbow. DO NOT glue this connection (Designed for friction fit). See Figure 50-5. 6. Remove the wire/string. With the door in an open position, secure the VacuSweep ®...
  • Page 26: Assembling The Tubing System

    ASSEMBLING THE TUBING SYSTEM Once you have installed all your inlets, you can complete the network of tubing that connects your inlets to the power unit. This network consists of the following parts: 90° Elbows – Used for connecting the inlet lines to the branch lines. Also used for making smooth 90°...
  • Page 27 Joining Straight Lengths of Tubing Both branch lines and the trunk lines may require lengths of tubing longer than those 8´ sections supplied. Use stop couplings to join two straight lengths of tubing. Insert one end of the tubing into the stop coupling; join the second length of tubing into the other end of the stop coupling.
  • Page 28 Circumventing an Obstacle Wherever possible the branch lines should connect to the trunk line in straight paths. The fewer turns in a tubing system, the more efficient air flow. Accordingly, you should locate the inlets to avoid zig-zags in the branch lines. But, sometimes, when you just can’t avoid an obstacle, you are required to construct the tubing around it.
  • Page 29 Connecting the Low Voltage Wiring Ideally, you will run the wiring and make all the wiring connections after you have completed the tubing system. Of course, the inlet wiring must be run at the time the inlet tubing is threaded through the walls. Run the low voltage wiring along the trunk line;...
  • Page 30 Attach the tubing to the joists or ceiling with either perforated metal or support strapping (support strapping is available from NuTone). Make all branch line connections in the same way you would an attic installation. Make sure that all branch lines enter the trunk line at an angle that is at least levelled with the trunk line.
  • Page 31: Power Unit Installation

    VX475, VX550 & VX1000 models, make sure bag is installed properly on bag holder and holder is locked in upright position. For models VX475C, VX550C & VX1000C, make sure the cyclonic filter media is properly seated. See Homeowners Guide if necessary. Close the door.
  • Page 32: Tubing Connections At Power Unit

    CAUTION Models VX475, VX550 and VX1000 will attach to the upper intake connections. See Figure 53. Models VX475C, VX550C and VX1000C will attach to the lower intake connections. See Figure 54. 1. Using rubber coupling and hose clamp provided, attach the utility valve assembly with the vacuum trunk line feeding into the power unit.
  • Page 33: Wiring

    WIRING This section refers to Figures 55 and 56. Grounding Instructions—This appliance must be grounded. If it should malfunction or break down, grounding provides a path of least resistance for electric current, to reduce the risk of electric shock. This appliance is equipped with a cord having an equipment-grounding conductor and grounding plug.
  • Page 34: Final System Check

    FINAL SYSTEM CHECK Be sure all inlets are closed and soil bag (for VX475, VX550 & VX1000 models) is in place. Check switch on power unit for manual on/off operation. Check that indicator light on side of power unit is lit and is in green mode. Check each wall inlet to be sure contacts activate power unit when hose is inserted and switched on, if applicable.
  • Page 35: Warranty

    WARRANTY For Models VX475 & VX475C Two-Year Limited Warranty For Models VX550 & VX550C Four-Year Limited Warranty For Models VX1000 & VX1000C Eight-Year Limited Warranty Rev. 01/2008 Rev. 01/2008 Rev. 01/2008...
  • Page 36: Troubleshooting Guide

    TROUBLESHOOTING GUIDE Trouble 1. Loss or decrease of vacuum occurs. 2. Power unit does not start, or shuts off during normal operation with no LED showing red or illuminated. 3. Power unit fails to stop when the hose is removed. 4.
  • Page 37 Possible Remedy 1a. Remove disposable filter bag or empty debris bucket as described in Homeowner’s Guide and install replacement. 1b. Insert handle end of hose into utility valve at power unit. Turn unit on. This will reverse normal air flow through the hose and dislodge any clogs.
  • Page 38 NOTES...
  • Page 39 NOTES...
  • Page 40 926 W , WI 53027 TATE TREET ARTFORD NUTONE WARRANTY All VX Power Units are covered by a NuTone 2, 4, or 8 year warranty. Refer to your Model Number for which warranty you have. Tools and Accessories warranted for one year from date of purchase. See page 35 for details. Product specifications subject to change without notice.

This manual is also suitable for:

Vx475Vx550cVx475cVx550Vx1000

Table of Contents