Lennox LI009CI-160T432 Service Manual page 63

Hide thumbs Also See for LI009CI-160T432:
Table of Contents

Advertisement

6. Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:
60
20 minutes after the
complete unit is
powered off
Is the terminal FA for the
electronic expansion valve
connected correctly?
Yes
Resistances between the first four pins
close to the terminal hole and the fifth
pin are almost the same, less than 100
ohm.
Replace the electronic
expansion valve
If the fault is eliminated?
No
Replace the
control panel
AP1
If the fault is eliminated?
No
Coolant leakage, refilling
the coolant
End
Connect the
No
wires correctly
Yes
Yes
Service Manual
Installation and Maintenance

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents