Directional or non-directional earth-fault relay
Hide thumbs Also See for REJ 527:
Table of Contents

Advertisement

1MRS 751055-MUM
3.1.2.
3.1.2.1.
3.1.2.2.
3.1.2.3.
Directional or Non-Directional Earth-Fault Relay
Operator's Manual

Display

Display idle mode

Self-supervision tests are run during initialisation. After all tests are completed, the
display will return to idle mode showing the text ABB.
READY
START
TRIP
ABB
)LJ  'LVSOD\ LQ LGOH PRGH

Display test at power up

When the auxiliary voltage is connected to the protection relay:
1. The backlight goes on.
2. The LCD display is tested by inverting it for a short time.
3. The display returns to idle mode and the backlight turns off.
READY
START
TRIP
)LJ  'LVSOD\ WHVW DW SRZHU XS

Display backlight

• Normally the backlight of the display is off.
• When an arrow button on the MMI is pressed, the backlight turns on. If the MMI
panel has not been used for about 5 minutes, the backlight goes off automatically.
• A power saving built-in feature: pressing the [C] button switches the backlight
off within 20 seconds.
C
E
C
E
REJ 527
9