Directional or Non-Directional Earth-Fault Relay
Operator's Manual

Red indication LED

READY
START
TRIP
)LJ 
5HG LQGLFDWLRQ /('
TRIP indicator
• Indicator off:
• Normal operation mode. No protection function has tripped.
• Lit indicator:
• A protection function has tripped. The trip indication is latching, i.e. it must be
reset by pressing the [C] button or via serial communication. As long as the
protection function is active it is not possible to reset the trip indicator.
Further, the indicators may be reset via the binary input X2.1/17-18 by applying
control voltage to the input, provided switches SGB1/1...3 are in position 1.
The basic protection relay functions do not depend on the state of the operation
indicators, reset or non-reset. The relay is permanently operative.