Specifications - Mitsubishi Electric CITY MULTI PKFY-P NLMU Series Operation Manual

Air-conditioners for building application indoor unit
Hide thumbs Also See for CITY MULTI PKFY-P NLMU Series:
Table of Contents

Advertisement

Available languages

Available languages

8. Specifications

Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y, R2, Multi-S is as below.
Model
Power source (Voltage/Frequency)
Capacity (Cooling/Heating)
Dimension (Height)
Dimension (Width)
Dimension (Depth)
Net weight
Fan Airflow rate (Low-Middle2-Middle1-High)
Noise level (Low-Middle2-Middle1-High)
Note
1. Operation temperature of indoor unit.
Cooling mode: 15 °C WB (59 °F WB) - 24 °C WB (75 °F WB)
Heating mode: 15 °C DB (59 °F DB) - 27 °C DB (81 °F DB)
2. Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB (81 °F DB)/19 °C WB (66 °F WB), Outdoor 35 °C DB (95 °F DB)
Heating: Indoor 20 °C DB (68 °F DB), Outdoor 7 °C DB (45 °F DB)/6 °C WB (43 °F WB)
en
15
P04
<V/Hz>
<BTU/h>
4,000/4,500
6,000/6,700
<mm (inch)>
<mm (inch)>
<mm (inch)>
<kg (lbs)>
10.7 (23.6)
117-124-134-
141-155-173-
<CFM>
148
<dB>
22-24-26-28
22-26-29-31
P06
P08
Single, 208/230 V, 60 Hz
8,000/9,000
12,000/13,500
299 (11 - 25/32)
773 (30 - 7/16)
237 (9 - 11/32)
11.1 (24.5)
141-162-191-
152-191-244-
191
237
22-27-31-35
24-31-37-41
P12
P15
15,000/17,000
18,000/20,000
299 (11 - 25/32)
898 (35 - 3/8)
237 (9 - 11/32)
12.9 (28.4)
222-261-304-
240-293-360-
297
353
29-34-37-40
31-36-41-46
P18
438