EXPERT 2V3SA
1. From the main menu, select: INLET.
2. Use the navigation keys to select the fol-
lowing menus:
Reset Mode
Open/Close
Reset 1 5:00 PM
Reset 2 5:00 PM
Reset 3 5:00 PM
Reset 4 5:00 PM
Reset Now?
No
Reset delay
2 min
Disable if OutT°
is Below 10.0°F
(These menus are accessible if an inlet is enabled in
the User Setup Menu).
3. Set the following parameters:
Reset Mode — Select the desired reset
mode: "Open/Close" to reset the actuator
toward its nearest position; select "Close"
to reset the actuator toward its closed
position only or select "Off" to disable the
automatic reset.
Reset 1,2,3,4 — Set the times at which
resets are performed. The inlets reset up
to 4 times per day when the reset times
are set to different times. Set all 4 reset
times to the same time if you only want
the inlets to reset once.
Reset now? — Select "Yes" to reset the
actuator's position now.
Reset delay — During a reset, the controller
opens or closes the inlet during this delay, or
up until a limit switch is reached. The reset
delay should be set to the same time value
or higher than the total opening time (as
defined in previous section).
Disable if Out.T° is Below — To prevent
the inlet from closing against ice, the
controller can stop all inlet resets when
it is too cold outside. Set the outside
temperature below which inlet resets are
forbidden. Note that the inlet can still be
reset manually regardless of the outside
temperature. *This parameter is accessible if
an outside temperature sensor is enabled in the
User Setup Menu.
EXPERT 2V3SA, rev. 10
41