Specifications - Carrier 38VTA040 Installation, Start-Up And Service Instructions Manual

Air-cooled condensing unit
Table of Contents

Advertisement

TABLE 1 SPECIFICATIONS
MODEL
OPERATING WEIGHT
REFRIGERANT
COMPRESSORS
CONDENSER FAN
FAN MOTOR
CONDENSER COIL
CONNECTIONS
POWER SOURCE (V-Ph-Hz) Nominal
ABSOLUTE MIN - MAX VOLTAGE
MINIMUM CIRCUIT AMPS (MCA)
MAXIMUM OVERCURRENT PROTECTION (MOCP)
RLA : Rated Load Amps
Notes : 1) MCA values are used for sizing the field supplied wires.
2) MOCP values are used for sizing the field supplied standard fuses or circuit breakers.
FIG. 3
GROUNDING MOUNTING
kg
Type
Factory Charged kg
Type
Oil charged (l)
LRA
RLA
Power Supply
Type
Number
Blade dia. (mm)
Speed (rpm)
Drive
Type
Power Supply
FLA
Rows - fins/m
Face area (m
2
)
Type
Liquid, (mm)
Suction, (mm)
(V)
FLA : Full Load Amps
38VTA
040
050
86
96
R-22
1.0
Scroll
1.36
1.95
50.0
65.5
7.9
10.0
400-3-50
Propeller
1
609
710
Direct Drive
Permanent Split Capacitor
230-1-50
1.46
2 - 591
1.14
Flare
9.50
19.05
400 - 3 - 50
360-440
11.0
14.0
20
25
LRA : Locked Rotor Amps
FIG. 4
WALL MOUNTING
060
98
1.77
74.0
10.0
14.0
25
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38vta05038vta060

Table of Contents