Flame Presence Check - Riello RLS 190/M MZ Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner
Table of Contents

Advertisement

7.2.4

Flame presence check

The quantity of flame signal can also be checked through the
"Check Mode" function.
Check the level of the flame detection signal with the "Check
mode" function from the flame control: LEDS from 2 to 6 indicate
the flame signal level, respectively.
See "LED indicator and special function" page 36.
Check Mode
With burner flame on:
 hold the reset button on the flame control pressed for at
least 3 sec.;
 the button colour will change from green to yellow;
 each operating status signalling LED will be compared to
20% of the maximum brightness;
 press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDS.
Servomotor
Release cam 4)(Fig. 38) from the servomotor, by pressing and
shifting button 3)(Fig. 38) to the right. Manually rotate it
backwards and forwards to make sure it moves smoothly. Now
engage the cam again by shifting the button 2)(Fig. 38) to the left.
Combustion head
Open the burner and make sure that all components of the
combustion head are in good condition, not deformed by the
high temperatures, free of impurities from the surroundings
and correctly positioned.
Fan
Check to make sure that no dust has accumulated inside the fan
or on its impellers, as this condition will cause a reduction in the
air flow rate and provoke polluting combustion.
Maintenance
Flame inspection window
Clean the glass of the flame inspection window.
33