4.8

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram (Fig. 3), consult the
manufacturer.
The firing rates were obtained in special test boilers, according to
EN 676 standard.
In (Fig. 3) you can see the diameter and length of the test
combustion chamber.
4.9

Commercial boiler

The burner RLS 190/M MZ is suitable for operating on boilers
with combustion chamber with bottom outflow (three passes), on
which the best NO
emissions are obtained.
x
The boiler front door maximum thickness must not exceed 250
mm (Fig. 4).
4.10

Burner equipment

Flange for gas train . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Seal for flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Screws to fix the flange M 10 x 40 to the gas
butterfly valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 4
Thermal flange gasket . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Screws to fix the burner flange pipe coupling
to the boiler: M 16 x 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 4
Flexible hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 2
Nipples for flexible hoses with gaskets . . . . . . . . . . . . . . . No. 2
Instruction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
20164195
Technical description of the burner
10
GB
Example:
Output 650 Mcal/h
diameter 60 cm
length 2 m
MODULATING RATIO
The modulating ratio, obtained in the test boilers, according to
standard (EN 676 for gas, EN 267 for light oil), is of:
- 3 : 1 (gas);
- 2 : 1 (light oil).
250 mm MAX
D715
Fig. 3
D1079
Fig. 4