6.11

Burner operation

6.11.1 Burner start-up

0s:
Control remote control TL closes. Fan motor
start-up.
6s:
Servomotor start-up: turn to the right by 130°,
i.e. until the contact intervenes on cam I
(Fig. 38, on page 29). The air damper is posi-
tioned to MAX output.
48s:
Pre-purging stage with MAX output air deliv-
ery. Duration 32 s.
80s:
The servomotor turns to the left to reach the
angle set on cam III (Fig. 38, on page 29) for
the MIN output.
112s:
The air damper and the gas butterfly valve
reach the MIN output position (with cam
III)(Fig. 38, on page 29) at 30°.
113s:
Ignition electrode strikes a spark.
119s:
The safety valve VS and the adjustment valve
VR open (quick opening). The flame ignites
with a small output - point A. The output grad-
ually increases, and the VR valve slowly
opens, until the MIN output is reached -
point B.
122s:
The spark goes out.
135s:
The start-up cycle ends.

6.11.2 Steady state operation

Burner without RWF50 output regulator
At the end of the start-up cycle, the servomotor control switches
to TR remote control that controls the pressure or temperature in
the boiler, point C. (The electric control box carries on checking
the presence of the flame and the correct position of the air and
gas maximum pressure switches).
If the temperature or pressure is low (so the TR remote
control is closed), the burner progressively increases the
output up to the MAX value (section C-D).
If the temperature or pressure then increases until the TR
opens, the burner progressively decreases its output to the
MIN value (section E-F). And so on.
Start-up, calibration and operation of the burner
20156543
Fig. 42
The burner locks out when the heat request is less than the
heat supplied by the burner at MIN output, (section G-H). The
TL remote control opens, the servomotor returns to angle 0°
limited by the contact of cam II page 29. The air damper
closes completely to reduce heat losses to a minimum.
With each change of output, the servomotor automatically
modifies the gas output (butterfly valve) and the air flow rate (fan
damper).
Burner with RWF50 output regulator
See the manual supplied with the adjuster.

6.11.3 Ignition failure

If the burner does not ignite, it locks out within 3s after the gas
valve opens, and the post-purging phase starts lasting 17s, i.e.
122s from TL closure.
Burner flame goes out during operation
If the flame goes out during operation, the burner will lock out
within 1s.

6.11.4 Final checks (with burner operating)

Disconnect a wire of the minimum gas pressure switch:
Open TL remote control:
Open TS remote control:
the burner must stop
Disconnect the P shared wire of the maximum gas pressure
switch:
Disconnect the P shared wire of the air pressure switch:
Disconnect electrically the sensor for the flame detection
the burner must stop in lockout
Make sure that the mechanical locking systems on the
adjustment devices are fully tightened.
31
GB
20156544
Fig. 43
20164195