ABB ACS860 Firmware Manual page 262

Primary control program
Table of Contents

Advertisement

262 Parameters
No.
Name/Value
58.36
EFB comm
supervision force
Bit
Name
0
Ext 1
1
Ext 2
2
Local
3...15
Reserved
0000b...0111b
58.101 Data I/O 1
None
CW 16bit
Ref1 16bit
Ref2 16bit
SW 16bit
Act1 16bit
Act2 16bit
CW 32bit
Ref1 32bit
Ref2 32bit
SW 32bit
Act1 32bit
Act2 32bit
CW2 16bit
SW2 16bit
RO/DIO control
word
AO1 data storage
AO2 data storage
Other
Description
Activates fieldbus communication monitoring separately for
each control location (see section
control
on page 20).
The parameter is primarily intended for monitoring the
communication with EFB when it is connected to the
application program and not selected as a control source by
drive parameters.
Value
1 = Communication monitoring active when Ext 1 is being used.
1 = Communication monitoring active when Ext 2 is being used.
1 = Communication monitoring active when local control is being
used.
EFB communication monitoring selection.
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400001.
The master defines the type of the data (input or output). The
value is transmitted in a Modbus frame consisting of two 16-
bit words. If the value is 16-bit, it is transmitted in the LSW
(least significant word). If the value is 32-bit, the subsequent
parameter is also reserved for it and must be set to None.
None.
Control Word (16 bits).
Reference REF1 (16 bits).
Reference REF2 (16 bits).
Status Word (16 bits).
Actual value ACT1 (16 bits).
Actual value ACT2 (16 bits).
Control Word (32 bits).
Reference REF1 (32 bits).
Reference REF2 (32 bits).
Status Word (32 bits).
Actual value ACT1 (32 bits).
Actual value ACT2 (32 bits).
Control Word 2 (16 bits).
When a 32-bit control word is used, this setting means the
most-significant 16 bits.
Status Word 2 (16 bits).
When a 32-bit control word is used, this setting means the
most-significant 16 bits.
Parameter
10.99 RO/DIO control
Parameter
13.91 AO1 data
Parameter
13.92 AO2 data
Source selection (see
Terms and abbreviations
Local control vs. external
word.
storage.
storage.
on page 92).
Def/FbEq16
0000b
1 = 1
CW 16bit
0
1
2
3
4
5
6
11
12
13
14
15
16
21
24
31
32
33
-