104 Parameters
No.
Name/Value
06.16
Drive status word 1
Bit
Name
0
Enabled
1
Inhibited
2
DC charged 1 = DC circuit has been charged. If present, the DC switch is closed, and
3
Ready to
start
4
Following
reference
5
Started
6
Modulating
7
Limiting
8
Local control 1 = Drive is in local control
9
Network ctrl 1 = Drive is in
10
Ext1 active
11
Ext2 active
12
Reserved
13
Start request 1 = Start requested
14...15 Reserved
0000h...FFFFh
Description
Drive status word 1.
This parameter is read-only.
Description
1 = Both run enable (see par. 20.12) and start enable (20.19) signals are
present, and Drive interlock has not been activated.
Notes:
• In I/O or local control, clearing this bit makes the drive enter the
SWITCH-ON INHIBITED state (see page 414).
• This bit is not affected by the presence of a fault.
1 = Start inhibited. See parameters
inhibiting signal.
charging switch is open.
0 = Charging not complete. If the inverter unit is not equipped with a DC
switch (option +F286), check setting of 95.09.
1 = Drive is ready to receive a start command
1 = Drive is ready to follow given reference
1 = Drive has been started
1 = Drive is modulating (output stage is being controlled)
1 = Any operating limit (speed, torque, etc.) is active
network control
1 = Control location EXT1 active
1 = Control location EXT2 active
Note: At the time of publishing, a start request from the control panel does
not activate this bit if any start-inhibiting condition (see bit 1) is present.
Drive status word 1.
06.18
and
06.25
for the source of the
(see page 14)
Def/FbEq16
-
1 = 1