11.2 Error temperature sensor

No
Mount sensor or
check settings
O.K.
Operating temp.
Resistance
T
(°C)
oper
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
Table 5: Resistance value
58
Error temperature sensor
T1 / T2 / T3 / T4 / T5
Sensor
connected
according to circuit
diagram?
No
Correct
settings
R
(k)
25
129,30
96,36
72,50
55,05
42,16
32,56
25,34
19,87
15,70
12,49
10,00
8,059
6,535
Error handling
Yes
Check settings
Check
resistance
Yes
(table 5)
O.K.?
Change the
slave board
WARNING!
Do not touch the board
for under 230 V power
supply live components!
Yes
No
Change
the sensor