Paul CLIMOS F 200 Basic Service Instructions Manual page 56

Mechanical ventilation heat recovery unit
Table of Contents

Advertisement

Error description /
message on display
Error sensor 1
Error sensor 2
Error sensor 3
Error sensor 4
Supply air temperature
too low
Intake air temperature
too low
Error fan 1 Hall
Error fan 2 Hall
Communication error
No external release
Table 4: Overview of messages, error visualisation and error treatment by means of the TFT touch panel
56
Messages, errors and error handling
Reason
Sensor break or short circuit
temperature sensor T1
Sensor break or short circuit
temperature sensor T2
Sensor break or short circuit
temperature sensor T3
Sensor break or short circuit
temperature sensor T4
Minimum supply air
temperature < setpoint;
Factory setting 5 °C
Current intake air
temperature < setpoint
longer than 10 minutes
Supply air fan speed does
not report
Exhaust air fan speed does
not report
BUS components of the
controller are not detected
Release contact open
Reaction
Fans are turned off
Fans are turned off
Fans are turned off
Fans are turned off
Fans are turned off
Fans are turned off
Fans are turned off
Fans are turned off
Fans are turned off
Fans are turned off,
no control by external
control unit
Control / Action
Check or replace sensor
Check or replace sensor
Check or replace sensor
Check or replace sensor
Supply air temperature
> setpoint + 1 K
Intake air temperature
> setpoint;
control after 1 h
manual adjustment of
an speed
manual adjustment of
an speed
Restart (Off / On) of the
device
Close release contact