Using Copy Mode
This function can be used only when control is stopped. When copying settings, first finish making settings for the Temperature Controller in the
normal mode, then upload and download in Copy Mode.
Upload (Temperature Controller to
Setting Display Unit)
0
Step 1
Press the COPY Key for at least 1 s to enter Copy Mode.
Step 2
Use the UP and DOWN Keys to select up on Display No. 2. Press the
UNIT Key to select the unit number for the upload.
Any unit number from 0 to f or "-" (all units) can be selected.
Step 3
Press the LEVEL Key for at least 1 s to start the upload.
Note: 1. up will flash on Display No. 2 during the upload.
2. The mode will return automatically to the Operation Level
when the upload has been completed.
Download (Setting Display Unit to
Temperature Controller)
0
Step 1
Press the COPY Key for at least 1 s to enter the copy mode.
Step 2
Use the UP and DOWN Keys to select down.
The possible selections are up and down.
Step 3
Press the UNIT Key to select the unit number for which data has
been uploaded. Any unit number from 0 to f can be selected (for
each Unit). The unit number for any Controllers without uploaded
data, however, will not be displayed. Also, selection will not be
possible if the uploaded information in the display was uploaded from
all Controllers. The UNIT display will be "-".
Note: For example, to download setting data from unit number 1 to
unit number 2, change the unit number from 2 to 1, and change
the number of unit number 1 to another unit number or
disconnect the socket connected to unit number 1. Be sure that
there is only one Controller with the same unit number on the
network at any one time.
Step 4
Press the LEVEL Key for at least 1 s to start the download.
Note: 1. down will flash on Display No. 2 during the download.
2. The mode will return automatically to the Operation Level
when the download has been completed.
Supplementary Explanation
To download to all Temperature Controllers, use the same
configuration as when the data was uploaded. Downloading is not
possible in the following circumstances. If downloading is not
possible, down will flash and then the upload display will be shown.
copy
up
copy
down
• An E5ZN has been added or deleted since the upload.
• The same number of Controllers are connected as when the
upload was executed, but when the unit numbers are different.
• The resistance thermometer/thermocouple type configuration is
different.
Copying Parameters from an E5ZN
Master to Other E5ZNs
This section describes how to copy parameters from Unit 1, used as
the master, to Units 2 and 3, as shown in the following diagram.
System Configuration
23
0
0
E5ZN-SDL
Data uploaded to the E5ZN-SDL can be downloaded only to a
Controller whose unit number has been uploaded. Therefore, after
copying the Master parameters, change the unit number of the
Controller where the data is to be downloaded to the unit number
from which data was uploaded (i.e., the master's unit number), and
then download the parameter data.
Step 1
0
Select Copy Mode.
Press the COPY Key for at least 1 s to enter Copy Mode.
Step 2
1
Press the UNIT Key to select the unit number of the master. In this
example, the master is unit number 1, so select 1.
Step 3
1
Upload all the parameters from the Master.
In this example, all the parameters from unit number 1 will be
uploaded to the E5ZN-SDL. Press the LEVEL Key for at least one
second to start the upload. up will flash on the display during the
upload.
The mode will return automatically to Run Mode when the upload
has been completed.
Master
23
0
copy
up
copy
up
6