1) Insert a minus screwdriver into the wire entry opening,
between the clamp and the housing, until its tip hits the
bottom where it is firmly held.
Tension Clamp
2) Insert a wire. Push the screwdriver toward the direction
indicated with the arrow in the figure below to widen the
opening if necessary.
Wire Entry
3) Confirm that the wire tip hits the bottom and pull out the
screwdriver in holding it in position.
Confirm that the wire's insulation tube is not caught in
the clamp.
Screwdriver
Wire
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
PC CONFIGURATOR
With configurator software, settings shown below are avail-
able.
Refer to the software manual of R6CON for detailed opera-
tion.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
Sensor type
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
S
C (WRe 5-26)
N
U
L
P (Platinel II)
(PR)
Lower range value
Depends on sensor type 0.00 (degC)
Upper range value
Depends on sensor type 0.00 (degC)
Fine zero adjustment
-320.00 to +320.00 (%)
Fine gain adjustment -3.2000 to +3.2000
Scaled range Zero
-32000 to +32000
Scaled range Span
-32000 to +32000
Burnout
Upscale, Downscale
■ CHANNEL BATCH SETTING
PARAMETER
AVAILABLE RANGE
Loss of internal bus
0.0 – 99.9 (sec.)
communication detec-
tion time
Conversion rate
250, 500 (msec.)
Temperature unit
degC, degF, K
CJC
ON, OFF
Limit
-15 to +115%
Scaled range Zero / Span
R6S-TS2
DEFAULT SETTING
K (CA)
0.00 (%)
1.0000
0
10000
Upscale
DEFAULT SETTING
1.0 (sec.)
500 (msec.)
degC
ON
-15 to +115%
EM-7781-BI Rev.3 P. 4 / 4