Installation Procedure
• Do not give the hose an upward gradient beyond
the connection port. This will cause water to flow
backwards when the unit is stopped, resulting in water
leaks.
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
NOTE
• If a concentrated drain pipe is installed, refer to the figure below.
Hanger
Main drainpipe
14
English
Under gradient
Ceiling
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
Individual air
vent
• Install horizontally.
Be horizontal
Indoor unit
• Max. allowable axis gap.
Indoor unit
• Max. allowable bending angle.
Indoor unit
1~1.5m
Centralized horizontal drainpipe
(more than 1/100 slope)
Flexible hose
Max. 20 mm
Main air vent
200 mm or more
300 to 550 mm