Removing and Replacing FRUs
Figure 9: DC Power Supply Terminal Block Ground Cable Lugs
Step 4
Insert the stripped end of the wire into the open end of the lug.
Step 5
Crimp the wire in the barrel of the lug. Verify that the wire is securely attached to the lug.
Step 6
Place the wire against the terminal block, making sure there is solid metal to metal contact.
Step 7
Secure the lug to the chassis with two M4 screws. Ensure that the lug and the wire will not interfere with other
switch hardware or rack equipment.
Step 8
Replace the snap on cover on the terminal block of the DC power supply.
Cisco Catalyst 8500 Series Edge Platforms Hardware Installation Guide
Wiring the DC Input Power Source
41