Alarm Messages - Elsteam HPN Series User, Installation And Maintenance Manual

High pressure proportional humidifier
Hide thumbs Also See for HPN Series:
Table of Contents

Advertisement

HighPressure Humidifier - Constant Pressure

10 Alarm Messages

Message
Insufficient Water
Lack of input water
Cause
Inverter security error
Check input water flow.
Check inverter display for error messages. If "Etb" message is displayed the output
pressure security pressure switch stopped the system. Check the output bypass valve.
Turn it counterclockwise to reduce output pressure.
Remove one nozzle from the network and try the system. Press OK key to remove
Possible Solution
alarm condition and restart the system.
If the alarm condition stops:
If the system is still in alarm, please contact ELSTEAM or your distributor for input flow
meter replacement part.
Message
Check Load Valve Driver
Cause
Driving of input water solenoid failure
If "W" character is displayed in the first line, check solenoid connections and voltage
(12V). Press OK key to remove alarm condition and restart the system.
Possible Solution
If the system is still in alarm, please contact ELSTEAM or your distributor for part
replacement.
Message
NTC failure
Cause
The pump temperature probe is damaged.
Possible Solution
Contact ELSTEAM or your distributor for part replacement.
Message
Low Output Pressure
Cause
The pressure in the nozzle pipe cannot reach the default value within the set period.
Possible Solution
Check distribution network and output connection pipe for draining.
Check the output bypass valve. To increase the output pressure turn clockwise the
valve.
Message
Pump Overheating, check atomizers
Cause
Pump temperature high.
Possible Solution
Check the output bypass valve. Turn it counterclockwise to reduce output pressure.
To remove alarm conditio0n and restart the system press OK key.
CAUTION
The controller stores the status of the humidifier in a FLASH memory.
Turning the system off and on to remove alarm conditions has no effect
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
Replace nozzle and restart the system
E-mail: info@elsteam.it - Web: http://www.elsteam.com
21.1.EN