Installation and Startup Guide
This document covers the installation of MT600iWP Series HMI, for the detailed specifications and
operation, please refer to Datasheet and MT600iWP User Manual.
Install Environment:
NEMA Rating
MT600iWP
HMI is NEMA 4X rated.
The
MT600iWP
Series has been tested to conform to European CE
Electrical
requirements. This means that the circuitry is designed to resist the effects of
Environment
electrical noise. This does not guarantee noise immunity in severe cases. Proper
wire routing and grounding will insure proper operation.
(1) Make sure that the displays are installed correctly and that the operating
limits are followed Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2)
Do not operate the unit in areas subject to explosion hazards due to
Environmental
flammable gases, vapors or dusts.
Considerations
(3) Do not install the unit where acid gas, such as SO2 exists.
(4)
This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5)
Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
Unpacking the Unit
2
Unpack and check the delivery. If damage is found,
notify the supplier.
(1)
(2)
(3)
(5)
(4)
Installation Instruction
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
(1) Installation Instruction, 2-sided A4 *1
(2) MT600iWP HMI *1
(3) Power Connector *1
(4) Brackets & Screws V2.1 *1 pack
(5) Fuse 1.25A/250V 5*20mm *1
Installation Instructions
3
Secure the operator panel in position,
using all the fastening holes
and the provided brackets
and screws:
(A)
Cutout
(B)
Type
A(mm)
B(mm)
MT605iWP
119
93
MT607iWP
192
138
MT610iWP
259
201
4
Power Connections
5
Settings Introduction
When HMI is ON, the relevant
system settings are accessible.
( Note 1: For the details of HMI
DIP SW function settings please
refer to Part 8 in this guide. )
NOTE:
Connect positive DC line to the '+24V'
1.
terminal and the DC ground to the '0V' terminal.
2. Please do not connect HMI with PLC and PC
simultaneously to prevent potential difference
from destroying USB ports of HMI and PC.
To make a connection, strip about 3/8" of
insulation off the end of the wire, turn the
connector screw counterclockwise until the gap
is wide open, insert the wire all the way in, and
turn the screw clockwise until it's tight.

Advertisement

loading

Summary of Contents for weintek MT600iWP Series

  • Page 1 Installation Instruction and screws: Installation and Startup Guide Cutout This document covers the installation of MT600iWP Series HMI, for the detailed specifications and operation, please refer to Datasheet and MT600iWP User Manual. Type A(mm) B(mm) Install Environment:...
  • Page 2 This product is limited warranted against defects in design and manufacture. The proven Hide HMI System Setting Bar defective product will either be repaired or replaced, at Weintek’s discretion. This warranty Boot Loader Mode shall not cover any product which is MT607iWP/MT610iWP Normal (a) Out of warranty period which is 1 year from the date of purchase.