Appendix B - circuit breaker
rejection features
General
96
In general, draw-out breakers of the same type
Circuit breaker
and rating are interchangeable in their equipment
pin assembly
compartments; draw-out breakers of different
types or short circuit ratings are intentionally made
97
non-interchangeable. To prevent inserting the
Cradle pin assembly
wrong breaker into a draw-out compartment,
unique "rejection hardware" is affixed to each
breaker and its cradle. The rejection is
accomplished by pins on the sides of the breaker
and on the sides of the cradle.
Rejection feature
This factory-installed, pin and gate device
prevents the insertion of a circuit breaker into
a cradle if the nominal rating of the breaker
is incompatible with that of the cassette and
its ancillary equipment.
The information in the following appendices
lists the available rejection scheme combinations
for the rejection feature. Rejection combinations
are in Appendix C.
1
1. Breaker pins (shown)
96
1
1. Cradle pins (not shown)
97