I N S TA L L AT I O N , O P E R AT I O N S A N D M A I N T E N A N C E M A N U A L
Padlocking the cradle
94
The circuit breaker compartment door must be
Compartment
padlock device
opened to put the padlock on; however, there is no
interference with the door after the padlock has
95
been placed in position. Padlocks will prevent the
Shutter padlocking
acceptance of breakers in the cradle. The padlock
device on the cradle will accept up to three
padlocks on both the left and right sides of the
cassette. See Figure 94.
94
1. Provisions for padlocks (not shown)
Padlocking the shutter
The shutter on each cubicle can be padlocked to
prevent access to the live primary conductors.
The breaker must be removed from the
compartment to padlock the shutter. For E2.2 and
E4.2 cradles, a minimum of 2 padlocks are required
(one for the top shutter assembly and one for the
bottom shutter assembly).
For E6.2, a minimum of 4 padlocks are required (2
for the 2 top shutter assemblies and 2 for the 2
bottom shutter assemblies). See Figure 95 for
reference on how to install a padlock on the shutter.
Removing the shutter unit
Refer to 1SDH001400R0831 for full instructions on
the removal of the shutter unit.
1
DANGER
Warning: Unless the proper
WARNING
precautions are taken, the removal of
a shutter unit presents the hazard of
CAUTION
electrical shock and burn. Do not
remove the shutter unit unless the
NOTICE
equipment has been deenergized.
Failure to do this can result in serious
injury.
95
Installing the shutter unit
Refer to
1SDH001400R0831
installation of shutter units. Available shutter
units are listed below in Table 10.
Table 10 - Emax 2 shutter catalog numbers
Size
Type
shutter top or bottom
E2.2
E2.2 FP 3p ReliaGear LV SG
shutter top
E4.2 FP 3p ReliaGear LV SG
E4.2
shutter bottom
E4.2 FP 3p ReliaGear LV SG
shutter top
E6.2 FP 3p ReliaGear LV SG
E6.2
shutter bottom
E6.2 FP 3p ReliaGear LV SG
DANGER
Warning: Unless the proper
WARNING
precautions are taken, the
installation of a shutter unit presents
CAUTION
the hazard of electrical shock and
burn. Do not install the shutter unit
NOTICE
unless the equipment has been de-
energized. Failure to do this can
result in serious injury.
58
for full instructions on
Global ordering code
1SDA114343R1
1SDA114345R1
1SDA114346R1
1SDA114347R1
1SDA114348R1