Uni-P H20 200C DEHUMIDIFIER
7.Installation Dehumdifier
The Uni-P H2O 200CC can be installed in various locations in order to meet the needs
of the client. However, it is important to observe the factors highlighted below during the
installation process:
The device is designed to best suit indoor installation in a room that is protected
from flooding and rain.
Make sure you install the device in a room with enough space to allow easy access
to the side and back panels during service and installation. The space should also
allow easy access to the filter cover panel.
You should ensure that the air discharged by the device is not directed over water
in the pool areas, or at people.
Make sure that there are no possible chances that the device could be splashed
or fall into the water. Also, ensure that it is plugged into a GFI (Ground Fault Interrupter).
You should never use the device on a table or a bench.
You should not place the device directly to structural members.
Make sure you provide isolation to reduce operational noise and/or vibration.
The drain pan should always be placed beneath the dehumidifier unit if it is located
above a room where water leakage is more likely to occur.
Place the device on supporters that raise its base to at least 6" above the top flanges
on the drain pan below it. Raising the dehumidifier will help the device to drain water
freely with gravity.
The device can be suspended using a steel hanger or any other suitable alternative
from structural members, the unit should be supported from beneath. Ensure
that you do not hang from ends or sides.
Make sure that you place a drain pan beneath the dehumidifier if it is
suspended on top of a finished area or a space where water leakage is
more likely to occur.
7.1 Electrical Requirements
The device plugs into a NEMA rated receptacle. The number of Amps drawn by the
device may vary depending on the operational conditions. In most cases, a GFI
protected circuit is necessary. It is important to install the remote control panel in the
central area of the room where it will be able to sense the RH of the room on turning it on.
It is important to install the remote control panel in the central area of the room where it
will be able to sense the RH of the room on turning it on.
CAUTION:
In order to maintain proper drainage, it is advisable that the unit should be
mounted such that the drain outlet is 4" or more above the floor drain, and must be
totally supported beneath the base.
Tel: 888-990-7469
Installation, Operation & Service Instructions
2
Uni-P H20 200C DEHUMIDIFIER
7.2 Plug Holes Using
Coll the control panel and the dehumidifier. Make sure that you safely route the control wiring
to help avoid damage during the installation process.
Make sure you do not cross the wires when you are connecting the device and the remote
control panel too.
In most cases the remote control panels of the Uni-P H2) 200CC are powered by the low
voltage (24 VAC). It must never be connected to any sort of high voltage circuit. The
remote control and terminals are numbered and labeled to prevent confusion. Make sure
you read the electrical schematic available inside the access panel of the device or in this
manual before you make any control connections.
CAUTION:
In order to maintain proper drainage, it is advisable that the unit should be
mounted such that the drain outlet is 4" or more above the floor drain, and must be totally
supported beneath the base.
7.3 Condensate Water Removal
In normal cases the condensate drain by the aid of gravity through the drain port. It is
advisable that you make use of the 3/4" male PVC NPT pipe. Also, rout the drain pipe
and ensure it is draining well. If possible, install a trap too. You should always be careful
when installing the drain pipe to the drain port. You can use an adjustable wrench to
safeguard the drain port. In addition, an optional water pump kit can be installed in a
case where a lift is necessary for disposing of the condensate. You can order the
condensate pump kit from Uni-P Dry.
During the installation of the drain hose ensure that the base of the device is at least 6"
above the ground. After this, coil the drain hone beneath itself or just position a spacer
to lift the hose at least 1" above the ground after the hose gets in contact with the
ground. This process will create a trap that makes sure that the unit drains well.
7.4 Hanging Diagram
Opt.1 - Install P-trap (Not inluded)
3
Installation, Operation & Service Instructions
Opt.2 - Create trap out of hose
Tel: 888-990-7469