IBM OpenCAPI Installing And Servicing page 60

Adapter support for the 8335-gth system
Table of Contents

Advertisement

Slide rails
Use this procedure when your system is installed using slide rails.
Before you begin
When you place the system in the operating position, ensure that the cables at the rear of the system do
not catch or bind as you push the system unit back into the rack.
Procedure
1. Unlock the blue rail safety latches (A) by lifting them upward.
2. Align the system unit on to the rails and push the system unit back into the rack until both release
latches lock into position.
See Figure 33 on page 46.
Figure 33. Placing the system into the operating position
3. Replace the screws on either side of the system that secure the system to the rack.
46 Power Systems: Installing and Servicing the OpenCAPI adapter support for the 8335-GTH system