Siemens Echomax XRS-5 Operation Manual page 7

Hide thumbs Also See for Echomax XRS-5:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Mounting
Mount the transducer so that it is above the maximum material level by more than the
blanking value for accurate results. Refer to the associated transceiver manual for
information on setting the blanking value.
The transducer must be mounted so that the axis of transmission is perpendicular to the
liquid's surface.
Do not over tighten mounting. Hand tightening of the mounting hardware is sufficient.
Consider the optional temperature sensor when mounting the transducer.
Suspended Conduit
Flexible conduit transducer should not be
subjected to wind, vibration or jarring.
Submersible
Submersible transducer, used in
applications where flooding is possible.
7ML19985QT81
XRS-5 Series Transducers – OPERATION MANUAL
rigid metal
conduit
coupling
transducer
rigid metal
conduit
coupling
submergence
shield
Bracket
flexible conduit
steel channel
coupling
transducer
Plywood
coupling
Plywood mounting provides excellent isolation,
but must be rigid enough to avoid flexing if
subjected to loading.
Page EN-5

Advertisement

Table of Contents
loading

Table of Contents