Opening An Intake; Miv Manual/Physical Procedures; Miv Sam Manual Mode Procedures; Figure 98. Intake Close/Open Icon Group (Open) - Idex HALE SAM Operation Installation Maintenance Manual

Hide thumbs Also See for HALE SAM:
Table of Contents

Advertisement

6.3.2.1

Opening An Intake

DO NOT RUN THE PRIMER FOR MORE THAN 45 SECONDS. IF PRIME IS NOT ACHIEVED
IN 30–45 SECONDS, STOP AND LOOK FOR AIR LEAKS OR BLOCKED SUCTION HOSE.
A SAM equipped apparatus utilizes two (2) types of intake valves: Master intake valves and auxil-
iary (Pony) valves. There are three (3) separate ways to manually open an intake valve (master
intake valve or Pony) on a SAM equipped apparatus. Two (2) methods are electronic and one (1)
method is physical.
6.3.2.1.1

MIV Manual/Physical Procedures

There are two (2) methods to electronically open/close an MIV in SAM Manual Mode. See the fol-
lowing subparagraphs for non-automated (manual) MIV operating procedures. For MIV physical
override procedures, see paragraph 6.3.6.1 (page 103).

6.3.2.1.1.1 MIV SAM Manual Mode Procedures

Perform the following, as applicable and/or as desired, to electronically open a master intake
valve. Use Step A to manually open an MIV from the SAM Control Center or Step B to open an
MIV from the associated MIV-2.0 placard (located on the apparatus panel at the MIV).
A. On operator panel, using SAM Control Center, open desired intake as follows.
Display MANUAL VALVE CONTROL screen as follows.
a) On SAM Control Center (from the SAM landing screen or from Auto Mode Home
screen) touch MANUAL MODE button. (See Figure 56, page 56.)
b) Touch YES button on acknowledgment popup. (See Figure 57.)
Touch and hold + button on valve close/open icon group (Figure 98) for de-
sired master intake valve. (All progress bars eventually illuminate and the +
button transitions to the VALVE OPEN indicator. The VALVE CLOSED indicator
transitions to the—button as soon as the valve partially opens.)
Figure 98.
B. On associated MIV 2.0 placard (reference SAM Parts Manual, FSG-MNL-0212),
open desired master intake valve as follows.
On the associated MIV 2.0 placard, if the green indicator portion of the OPEN/CLOSE
rocker switch is illuminated, the valve is already fully open.
Intake Close/Open Icon Group (Open)
NOTE
83

Advertisement

Table of Contents
loading