TEST RUN

Before test run
Before turning on the power supply, carry out
the following procedure.
1) By using insulation tester (500VMΩ), check
that resistance of 1MΩ or more exists
between the terminal block L to N and the
earth (grounding).
If resistance of less than 1MΩ is detected,
do not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
To protect the compressor at activation time,
leave power-ON for 12 hours or more before
operating.
Before starting a test run, set addresses by
following the Installation Manual supplied with
the outdoor unit.
Requirements for turning thermostat
OFF
Cooling operation
When the outdoor/suction air temperature is
lower than or equal to 19 °C.
When the outdoor/suction air temperature
is lower than or equal to 3 °C above the set
temperature.
Heating operation
When the outdoor/suction air temperature is
lower than or equal to -10 °C
When the outdoor/suction air temperature is
higher than or equal to 15 °C.
When the outdoor/suction air temperature is
higher than or equal to 3 °C above the set
temperature.
Execute a test run
When a fan operation is to be performed for an
individual indoor unit, turn off the power, short
circuit CN72 on the circuit board, and then turn
the power back on. (Set the operation mode to
"fan" to operate the unit.) When the test run has
been performed using this method, be sure to
release the short circuit of CN72 after the test
run is completed.
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the
Owner's Manual attached to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by
thermostat-OFF.
In order to prevent a serial operation, the forced
test run is released after 60 minutes have passed
and returns to the usual operation.
Do not use the forced test run for cases
other than the test run because it applies an
excessive load to the devices.
33-EN
CAUTION
Wired remote controller
Be sure to stop the air conditioner before
making settings.
(Change the setup while the air conditioner is not
working.)
1
Push and hold OFF timer button and
[
] setting button simultaneously
for 10 seconds or more. [TEST] is
displayed on the display part and the
test run is permitted.
2
Push ON/OFF button.
3
Push menu button to select the
operation mode. Select [
or [
Heat] with [
button, and then push menu button
(three times) again to determine the
operation mode.
Do not run the air conditioner in a mode
other than [Cool] or [Heat].
The temperature setting function does
notwork during test run.
The check code is displayed as usual.
4
After the test run, push OFF timer
button to stop a test run.
([TEST] disappears on the display and the air
conditioner enters the normal stop mode.)