Installation; Configuration Of Climatix Controller - Mandik CP-M-B Manual

Wall-mounted control
Table of Contents

Advertisement

KJM MANDÍK Controlling with CPM Wall-Mounted Control
5

Installation

The CP-M-B series wall-mounted control is designed for installation in indoor,
Installation
dry environments. It should be placed about 1.5 m above the floor at a place
with good natural air circulation. The unit is suitable for mounting on most
commercially available wiring boxes or directly on a wall.
When mounting the unit, the mounting plate must be fixed first. When the
electrical contacts are connected, the top panel is hung on the mounting plate
and clicked in place.
Opening
On the underside of the front cover there are two rectangular holes for a small
the cover
flat-blade screwdriver. Insert a screwdriver into each hole to release the inner
latches and to lift the front cover and then to take it off easily. Both the covers
are plastic.
Installation
The unit may only be opened by a qualified electrician.
Electrical installation must be performed in accordance with the relevant
principles
regulations and standards.
Connected cables must meet the insulation requirements of the mains voltage.
Note
Caution! The unit is not protected against accidental connection to ~ 230
V.
6

Configuration of Climatix Controller

Configuration
The Climatix controller must be correctly configured for Mandík air-conditioning
of Climatix
unit to operate correctly with a wall-mounted control. Configuration is performed
controller
at the factory based on customer requirements and an electrical diagram that is
part of the documentation supplied with a specific order. General configuration
steps are as follows:
- Selection, setting and assignment of an input for monitoring the desired
temperature.
- Selection, setting and assignment of an input for monitoring the desired
speed.
- Selection and assignment of an output for signalling unit operation.
- Selection and assignment of an output for signalling unit fault.
- Setting the temperature change range.
- Setting the desired speed change range.
- Selection of Comfort or Attenuation mode when the unit is on.
- Selection of Off or Tempering mode when the unit is off.
Prior configuring the Climatix controller, it is necessary to familiarize yourself
Note
with the manual 'Measurement and control system for MANDÍK air-conditioning
units - Detailed instructions and control'.
NONO_CP-M-B_2019-6
www.mandik.cz
6