Majestic MERCURY Series Installation Manual page 19

Hide thumbs Also See for MERCURY Series:
Table of Contents

Advertisement

1. Top Vent - Horizontal Termination
One Elbow
Note: Use SLP Series
components only.
Fire Risk.
• When using SLP-HRC-SS termination cap on top
vented fireplaces, a one foot minimum vertical
vent section is required before installing first
elbow.
• Elbow heat shield required when V1 is less than
1-1/2 ft. Clearances to combustibles MUST be
maintained. See Section 5.A.
**
Note: When using SLP-FLEX (6-5/8 in.) venting, there
MUST be a 25% reduction in total H when using flex vent.
Figure 4.11
WARNING*
Majestic • MERC32IN, MERC32IL Installation Manual • 2401-980 Rev. L • 1/21
H
1
*
V
Minimum
H
Maximum
1
1
90 Elbow Only
2 ft.
1/2 ft.
152 mm
2 ft.
1-1/2 ft.
457 mm
3 ft.
2-1/2 ft.
762 mm
5 ft.
3-1/2 ft.
1.1 m
7 ft.
4-1/2 ft.
1.4 m
15 ft.
H
MAX. =15 ft. (4.6 m)
1
V
+ H
MAX. = 40 ft. (12.2 m)
1
1
*
See Warning.
V
1
**
610 mm
610 mm
914 mm
1.5 m
2.1 m
4.6 m