Honeywell Ex-Or MSB1000DT Installation And Commissioning Instructions page 7

Advertisement

Parameter
Options
Power Up
On / Off
Response
Auto / Semi-auto
Off Delay
1 min-96 hrs (QuickSet Pro)
5, 10 or 20 mins (HP18)
Start Lamps
Max / Min
Entry Scene*
1-6
Bright Out
Yes / No
Dimming*
Reg 50%-Reg100%
Lamp Max*
10%-100%
Fade to Off
Yes / No
When Vacant
Off / Min / Reg <25% / Scene 6 (latter via
QuickSet Pro only)
Upper/Lower
0-254
Threshold
* These parameters are programmable using the QuickSet Pro only
Additional feature accessible under Utilities on QuickSet Pro:
100 Hour Burn-In Burn-in 100 hrs / Cancel / Resume
Important Additional Notes
1.
A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
2.
The dimming control output should be connected only to the control input of the ballasts - never to other detectors.
3.
This equipment should be used to control only those ballasts powered from the same phase as the detector
4.
Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains
with regard to wiring practice. The 0V line of the dimming output is almost at Neutral potential.
5.
DSI/DALI wiring to be on mains-rated safety wire.
6.
Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on
the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent.
Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.
7.
This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of
some particular lighting types (e.g. '2D' luminaires) may specify a maximum number of switching cycles in order to achieve a
predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic
controls in this respect.
8.
In order to achieve satisfactory light-level regulating operation, a detector must observe a substantially greater proportion of
artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its control.
Pre-Set
Notes
Sets the luminaire state at power up irrespective of occupancy.
On
Useful in reducing start-up load following power cut. Power-
up off - responds to occupancy after 30 seconds.
Auto
If set to auto, the presence detector switches the luminaire on
and off automatically. If set to semi-auto, the luminaire will not
turn on automatically when a person enters the area. It can be
turned on using the hand-held controller or by toggling the
power switch. When the area is vacated, the light will turn off
automatically.
20 mins
The time for which the luminaire will stay on following the last
detected movement. Also 10-second setting for walk-testing.
Max
Sets the level at which the lamps strike when turning on.
Scene 1
Sets which scene is recalled when unoccupied area is
entered.
No
If set to yes, movement fails to refresh the off delay if ambient
light level exceeds 125% of set level and the luminaire will
switch off when the off delay has elapsed. NB: Dimming must
be set to 100%.
100%
Can be set to operate between 50% and 100% ballast output
from max down to a bottom-end limit when working on
photocell control.
Can be set to limit the absolute maximum output of the ballast
100%
in all operating modes.
No
When no presence is detected, and after the off delay period,
the lamps can fade out instead of switching off (approx 80
seconds to fade from 100% to 0%).
Off
Options for a vacant area after it has timed out. Luminaires
can turn off, remain at minimum output, or regulate with a 25%
output limit, until the next period of occupancy. If programmed
to remain at minimum, to regulate below 25% (or go to scene
6 - available via QuickSet Pro only), there is an option to switch
off after 3 times the Off Delay (XTN).
254
Point at which photocell switches lights on/off.
0 hr
See Application Note: AN4028
- 7 -