Setting the Regulating Photocell
This product is intended for use with high frequency regulating ballasts with digital control inputs. An infrared
programming tool QuickSet Pro or HP18 is required for programming the regulating light level set point.
The setting is preserved in the event of a power failure and can be re-programmed any number of times.
Using the QuickSet Pro: Enter the Utilities menu, then choose 'LightSpot/MLS/LCM' and select 'Set Light Level'.
Use the 'up' and 'down' buttons to manually adjust the light output from the luminaire(s) and when at the required
level press and hold 'OK' to store.
On the HP18 Programmer, use the '+' and '-' buttons to manually adjust the light output from the luminaire(s) and
when at the required level press 'ü' to store. The luminaire(s) will blink to acknowledge a successful store
operation.
Sensor Positioning Notes
The majority of light seen by the photocell must be from the batten under its control - not that contributed by
another device (see Fig. 10 ).