Walk Testing
In order to verify the installation, there is an inbuilt facility (Walk Test Mode) to temporarily reduce the time
delay to 10 seconds. A QuickSet Pro or HP18 Programmer is required to access this facility.
Using the HP18:
Press the 'TEST' button to enable walk test mode.
Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before
moving and triggering the lights back on.
Re-programme the desired Off Delay once testing is complete.
Using the QuickSet Pro:
Go to the Utilities menu, choose 'LightSpot/MLS/LCM', then 'User Test', place the cursor over 'Walk Test',
point at the detector and press OK.
Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before
moving and triggering the lights back on.
After 5 minutes, the time-out will be restored to what it was before walk test was enabled.
Notes on Walk Testing:
During walk test, after the lights have turned off, wait 5 seconds before moving again because the sensitivity
l
is deliberately reduced for a few seconds following switch off.
Sensitivity is greater when approaching the circular footprint at a tangent rather than heading towards the
l
centre (see Fig. 7).
Most luminaires take approximately 1 second to strike after presence has been detected.
l
The detection pattern is cone-shaped which means that when standing at the very edge of the detection
l
footprint only a person's feet will be visible (see Fig. 8).
LED Operation
There is a blue LED on the detector which will flash when power is first applied or during a download from
the QuickSet Pro. If the LED is required to flash whenever movement is detected, please contact Technical
Support.
Commissioning
The factory default settings will be appropriate for most applications. However, the installer does have the facility
to re-program a wide range of parameters and to set the regulating light level using the infrared programming
tools. Please note that the full range of parameters is accessible via the QuickSet Pro; the HP18 offers
different/limited programming options.
Please read carefully the operating instructions that accompany the programmer prior to performing a
programming operation.
The following table shows the pre-set factory settings and a brief explanation of each parameter. These
parameters may be re-programmed any number of times and all settings will be retained in the event of a power
loss.