Commissioning
31. Tap
to save the set time. The set delay time is applicable for all the outputs.
NOTE: A single fire alarm in the zone will cause the programmable zone to be qualified.
CAUTION: THE MAXIMUM DELAY IS 10 MINS (600 SECS).
!
32. Go back to Zones, Devices & Onboard I/O screen. Refer Figure 5.3 on page 17.
33. Tap LOCAL INPUT. The following screen appears with Monitored input Tap
Monitored Input.
.
34. Tap CHANGE ZONE and ASSIGN a new zone.
35. To change the input action for the Monitored Input, tap EDIT ACTION and choose a new
input Action.
36. Go back to Zones, Devices & Onboard I/O screen, Refer Figure 5.3 on page 17. Tap
LOCAL OUTPUT. The following screen appears.