Honeywell STX Programming Manual page 36

Table of Contents

Advertisement

Commissioning
Option Title
Panel Description
Blank
Phone Number
Blank
Service Date
01 Jan 2000
No. of Fault Polls
4
Device Blinking
ON
Access Timeout
10 Mins 00
Sec
Log Diagnostic
OFF
Printer
ON
NOTE: If you select WIPE Config, the panel will return to the factory settings and all the existing settings will
be deleted automatically.
33
Table 6: Default Panel Settings
Setting
Default
Options
20 character
text
20 character
text
Date
4,5,6
ON / OFF
0 - 60 Mins
ON / OFF
ON / OFF
Description
Configure text for Pane Description to
be used.
Configure phone number of service/
maintenance provider.
Set service date based on agreed main-
tenance schedule. User can view this
information along with the Site Name
Reference and phone number of the
service provider.
Number of consecutive polls required
before device faults are reported.
This setting applies to: DEVICE LEVEL
FAULT, DOUBLE ADDRESS FAULT, NO
REPLY FROM DEVICE, BAD DEVICE
REPLY, DEVICE ADDED, DEVICE NOT
SUPPORTED, DEVICE TYPE CHANGED.
Determines if the detector's LED flashes
when the device is polled by the panel.
After Access Timeout period, screen
automatically logout and navigated
back to the main screen.
When set as ON, false alarm suppres-
sion algorithms are by-passed for faster
reporting of events.
Allows printing of the events reported in
the panel via an external printer, which
can be connected to the RS232 port of
the panel.