12) AC Wiring
A 2-way terminal block is provided on the AC Sontel for
power. There are 1-off Live and 1-off Neutral terminals in
total. A 2-way terminal is provided for Telephone Signal Input
Terminals
12.1 Wiring Diagrams
Telephone Signal
Input Terminals
Fig. 4 AC Terminals
13) Settings
13.1
Tone Selection
The sontels have 32 different tones that can be selected by
the DIP swirtches on the sounder pcb. The tone table on
page five shows the switch positions for the 32 tones and
which tones are available for the second and third stages. To
operate the sontel on stage one simply connect the supply
voltage to the normal supply terminals (+ve and –ve for DC
units, L and N for AC units).
13.2
Pulse Tone Operation
The BExTS110D Sontel has two modes of operation,
continuous tone operation and pulsed tone operation.
To select continuous tone operation the pulse tone header
pins should not be shorted. In this mode the output tone will
be as per the tone table.
To select pulse tone operation, the pulse tone header pins
should be shorted. In this mode of operation the selected
tone pattern will pulse on and off following the telephone
input signal.
Note if pulsed tone operation is selected it is advisable not to
select any of the intermittent tones, such as tone 11.
13.3
Volume Control
Warning - High noise levels above 85dB(A)
during operation. High levels of noise may
cause hearing loss, wear suitable ear
protection when equipment is in operation.
The output level of the BEx sontel can be set by adjusting the
volume control potentiometer (see Fig 9). For maximum
output, set the potentiometer fully clockwise.
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D210-00-021-IS
DIP Switch
Pulse Tone
Header Pin
L
N
AC Terminal
Issue 4
20-04-2020
Volume Control
Potentiometer
Fig. 9 Location of Volume Control Potentiometer ON
BExTS110D AC
14) Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
EN60079-19
Explosive atmospheres - Equipment repair,
IEC60079-19
overhaul and reclamation
EN 60079-17
Explosive atmospheres - Electrical
IEC60079-17
installations inspection and maintenance
To avoid a possible ELECTROSTACTIC CHARGE the unit
must only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed
prior to opening the unit.
Flameproof threaded joints and cemented joints are not
intended to be repaired.