Installation manual CF5-D, CF5-D-Disp / temperature transmitter for mounting in ventilation ducts Figure 1 1 Sampling probe 6 O-ring 29,2x3,53 (Factory supplied mounted in box) 2 Sealing gasket 7 PCB (Factory supplied mounted in box) 3 Largest locking nob 8 Snap-in lid...
Page 2
Mounting of CF5-D on to the duct. Figure 2 Hole with 25 mm diameter Temperature sensor with 110 mm cable mounted in the sampling probe Mounting Instruction Since there might be a substantial pressure difference in duct mounting applications, it is essential to avoid ambient air from suction into the duct mounting box. For correct function it is indispensable that the sealing of the box cover, the cable entry bushings, the cable feed through and the duct entrance are absolutely tight.
Page 3
(halfwave rectifier). Note 2: CF5-D can deliver a voltage or a current loop for Out(1) / Out(2). To change between voltage and current output mode the hardware jumpers are used. There is one jumper for Out(1) and one for Out(2), so that one output can be a voltage output and the other a current output.
Page 4
Terminals and jumpers on CF5-D. The darker positions are default settings. Dimensions Dimensions of sensor in mm and inches Dokument Page IMA 207 4 (4)